BRENNAN COMPANIES <br />..uf.; ,.a.: <br />BRENNAN C _'i5I uc1!ON <br />14 f.W Wulrr.t street Pule bu Mitrreiru MN' COI <br />BRENNAN PROPERTIES P]Olr6 4 ? rxrr411125 g teKtriariabCOlEMcent <br />Request For Information <br />TO: Bruce Schwartzman <br />CC: Scott Jones <br />FROM: Joe Brennan <br />DATE: 6/29/2015 <br />RE: RFI 14 - Ramsey Fire Station #2 <br />Inquiries: Please confirm two (2) 2 1/2" conduits are needed between back-up generator and <br />new Fire Station. Also, please confirm back-up generator location (closer to building, near <br />transformer, might be an option). <br />Suggestions: This question came from the electrical foreman. Additional conduit may be <br />required, depending on what equipment is on the back-up generator (e.g. block heater). <br />Generated By: Brennan Construction <br />Response: <br />PROVIDE (2) 20A/1 P CIRCUITS FROM PANEL P-1 FOR BATTERY CHARGER AND JACKET <br />HEATER. PROVIDE (1) 3/4" PVC CONDUIT FOR BATTERY CHARGER AND JACKET HEATER <br />CONDUCTORS. <br />SEE E400 FOR GENERATOR FEEDER CONDUIT SIZE AND GENERATOR CONTROL CONDUIT <br />SIZE (KEYNOTE #3). <br />GENERATOR SIZE HAS BEEN REDUCED FROM 150 KW TO 80 KW. REDUCE GENERATOR <br />BREAKER AND FEEDER FROM 400A TO 300A. <br />GENERATOR LOCATION TO REMAIN AS DESIGNED. CONFIRMED BY DEAN KAPLER AT 6/13/15 <br />O.A.C. MEETING. <br />Responded By: JOSH ORTMANN Date: 07-15-2015 <br />virwvir txcrtr14 cc:tay <br />