A3 Polyethylene (PE) Pressure Pipe and Fittings <br />Polyethylene pressure pipe and fittings shall be manufactured with compounds conforming to <br />ASTM D3350 and shall conform to ASTM D3035 and AVWVA C-901(for 0.5" to 3" diameters) <br />and ASTM F714 and AVWVA C906 (for 4" to 65" diameters) for the size, grade and pressure <br />class indicated on the plans, specifications and special provisions. Polyethylene pipe and <br />fittings shall be PE 3608 or PE 4710 for potable water transmission and pressure rating of one <br />hundred sixty (160) psi or greater, unless otherwise provided in the special provisions. The pipe <br />and fittings shall be manufactured from the same resin type, grade, and cell classification. <br />Unless otherwise specified, the dimensions and tolerances of the pipe barrel should conform to <br />Ductile Iron pipe equivalent outside diameters for pipe diameters greater than three inches (3"). <br />The method of joining material shall be by the Thermal Butt- Fusion Method in accordance with <br />ASTM 3261. <br />The minimum "quick -burst" strength of the fittings shall not be less than that of the pipe with <br />which the fitting is to be used. <br />B Fire Hydrants <br />Fire hydrants shall be of the type, size, and construction specified in the Plans and shall <br />conform to the applicable requirements of AV VVA C-502. <br />Unless otherwise specified in the Plans, Specifications, and Special Provisions, hydrants shall <br />be furnished in conformance with the following supplementary requirements: <br />(1) Hydrants shall have a five inch (5") (nominal diameter) main valve opening of the <br />type that opens against water pressure. <br />(2) Hydrant barrels shall be two (2) piece, non -jacket type, with flanged joint above <br />finished grade line and with mechanical joint connection at the hub end for joining a <br />six inch (6") ductile iron branch pipe. <br />(3) Hydrant operating rod shall be equipped with a breakable joint coinciding with the <br />flange joint above the grade line. <br />(4) Hydrant bury length shall be measured from the bottom of the branch pipe <br />connection to the finished ground line at the hydrant. <br />(5) <br />Hydrants shall have two (2) outlet nozzles for two and one half inch (2-1/2") (I.D.) <br />hose connection and one outlet nozzle for four inch (4") (I.D.) steamer connection. <br />All outlet nozzle threads shall be National Standard Fire -Hose Coupling Screw <br />Threads (NFPA 1963). <br />(6) Hydrant operating mechanisms shall be provided with "0' ring seals preventing <br />entrance of moisture and shall be lubricated through an opening in the operating nut <br />or bonnet. <br />(7) <br />Hydrants shall be provided with outlets for drainage in the base or barrel, or between <br />the base and barrel, unless the Special Provisions require that drain outlets be <br />omitted or plugged. <br />Page 23 <br />