Laserfiche WebLink
COMMERCIAL SERVICE REPORT <br />Company Name <br />CITY OF RAMSEY, <br />Site Name <br />Site Address <br />CITY OF RAMSEY <br />7550 Sunwood Dr NW <br />ANOKA,MN 55303-5137 <br />Report Date <br />8/19/2019 <br />Customer PO Number <br />Order Number <br />Dan Bray <br />025B15294 / WO-01033184 <br />Site Contact <br />Dan Bray <br />Work Requested <br />Description 763-286-1294 The chiller is tripping out on low oil. <br />Site Safety Assessment <br />Identified Concerns <br />Equipment <br />None <br />Serial Number <br />4905Q90522 <br />Work Performed <br />Manufacturer <br />Carrier <br />Serial Number Date <br />4905Q90522 08/15/2019 <br />Equipment Type (Model Number) <br />Air Cooled Chiller (30XAA2406F-0-073) <br />Work Description <br />Arrived on site, checked in with <br />customer. Checked chiller and <br />found B circuit running and A <br />circuit in alarm, P.75 circuit A <br />low oil level. Trouble shoot <br />chiller, found leak on A circuit at <br />the discharge valve. Found <br />packing to be leaking, will need <br />to replace the valve. Low oil <br />level alarm may be cause from <br />low refrigerant charge. Will need <br />to reclaim and weigh remaining <br />charge, at this time we can <br />change the oil. Pressurize <br />system and blew out oil from oil <br />separator and compressor. <br />Install new discharge valve, <br />external oil filter and filter cores. <br />Technician <br />Anthony V Sparrow <br />Labor Type <br />ST <br />Labor Sub -Totals ST <br />TH <br />DT <br />TVL <br />Customer Signature Date Carrier Signature Date <br />8/19/2019 <br />Qty <br />2 <br />2 <br />0 <br />0 <br />0 <br />8/19/2019 <br />Equipment and/or Service <br />CCS-TCES 091418 <br />Carrier Commercial Service <br />