Laserfiche WebLink
3. 1"throw dead bolt <br /> 4. 6 pin cylinders <br /> 5. ANSI Al 15.2 strikes <br /> D. Interconnected locks shall accommodate center to center dimensions of 4" or 5-1/2" between <br /> deadbolt and latch. <br /> E. Provide guarded latch bolts for all locksets, and latch bolts with sufficient throw to maintain fire <br /> rating of both single and paired door assemblies. <br /> F. Length of strike lip shall be sufficient to clear surrounding trim. <br /> G. Provide wrought boxes for strikes at inactive doors, wood frames, and metal frames without <br /> integral mortar covers. <br /> 2.8 PULLS, PUSH BARS, PUSH/PULL PLATES <br /> A. Acceptable manufacturers and respective catalog numbers: <br /> Burns Hager Ives <br /> 1. PART 91 - Offset Door Pull (1" d ia., 10" ctc) PART 92- 3 PART 93- 1 PART 94 - 8190-0 <br /> 9C 2J <br /> 2. PART 95- Offset Pull / Push-Bar(1" dia., PART 96-4 PART 97- 1 PART 98 - 9190-0 <br /> 10" ctc Pull) 22 x 39C 59 <br /> 3. PART 99- Push Plate (.050 411X 1611) PART 100 - PART 101 - ? PART 102 - 8200 4 <br /> 4 OS4x16 x16 <br /> 4. PART 103- Push Plate (.050 611X 1611) PART 104 - PART 105- 20 PART 106 - 8200 <br /> 6 OS6x16 611X16" <br /> B. Adjust dimensions of push plates to accommodate stile and rail dimensions, lite and louver <br /> cutouts, and adjacent hardware. Where required by adjacent hardware, push plates shall be <br /> factory drilled for cylinders or other mortised hardware. All push plates shall be beveled 4 sides <br /> and counter sunk. <br /> C. Where possible, provide back-to-back, and concealed mounting for pulls and push bars. Push <br /> bar length shall be 3" less door width, or center of stile to center of stile for stile & rail or full glass <br /> doors. <br /> 2.9 COORDINATORS <br /> A. Acceptable manufacturers and respective catalog numbers: <br /> Ives Door Controls H <br /> 1. PART 107 - Bar PART 108 - ( PART 109 - 60 PART 110 -2 <br /> Coordinator OR x FL 0 x Filler 97D x 297F <br /> 2. PART 111 - Mount PART 112 - 1 PART 113 -A PART 114 -2 <br /> ing Bracket B Series B, C Series 97 Series <br /> B. Provide coordinators at all pairs of doors having automatic flush bolts and closers on the inactive <br /> leaf, and for pairs of doors having vertical rod/mortise exit device combinations with overlapping <br /> astragals. <br /> C. Provide appropriate filler bars, closer mounting brackets, carry bars, and special top latch <br /> preparations as required by adjacent hardware. <br /> 2.10 CLOSERS <br /> A. Acceptable manufacturers and respective catalog numbers: <br /> LCN Yale Norton <br /> PAF PART 116-4050/4050 PART 117 - R4400/P PART 118 - R7500/ <br /> EDA SRI R4400 SRI PR7500 SRI <br /> B. Door closers shall be independently certified by ANSI for compliance with ANSI A156.4, Grade 1 <br /> (2013). <br /> Ramsey Water Treatment Plant 0871 00 -8 DOOR HARDWARE <br /> Ramsey, Minnesota <br />