Laserfiche WebLink
Performance Summary For CU-3 <br />Project: Ramsey WTP <br />Prepared By: Tim May <br />System: 38AUD_014 <br />No. of Circuits: Dual Circuit <br />System Quantity: 1 <br />Altitude: 0.0 ft <br />EER @ ARI Conditions: 11.0 <br />IEER: 13.6 <br />Suction Line Loss: 1.4 °F <br />Typical Liquid and Suction Line Sizing <br />Pipe Length Liquid Line Size Suction Line Size <br />0 - 25 3/8 7/8 <br />26 - 50 3/8 7/8 <br />51 - 75 3/8 1 1 /8 <br />76 - 100 1/2 1 1 /8 <br />101 - 125 1/2 1 1 /8 <br />126 - 150 1/2 1 1 /8 <br />151 - 175 5/8 1 1 /8 <br />176 - 200 5/8 1 1 /8 <br />Refer to the 38AU installation instructions for installation specific line sizing guidance <br />Outdoor Unit Parameters <br />Unit Quantity: 1 <br />PartNumber: 38AUDT14A0A6-0A1 C0 <br />Unit Model: 38AUD <br />Unit Size: 12.5 Tons <br />Condenser Coil: AI/Cu <br />Voltage: 460-3-60 V-Ph-Hz <br />Total Clg Cap.(Gross): 145.7 MBH <br />SDT: 117.1 °F <br />Clg Ent Air DB: 91.0 °F <br />Saturated Suction Temp: 48.0 °F <br />Outdoor Electrical Data <br />Unit Voltage: 460-3-60 V-Ph-Hz <br />Unit MCA: 21.0 Amps <br />Unit MOCP: 25.0 Amps <br />Total Compressor Power of Unit: 10.00 kW <br />Voltage Range Min: 414 V <br />Voltage Range Max: 506 V <br />Compressor RLA: 8.4/8.2 <br />Compressor LRA: 66/66 <br />Compressor Quantity: 2 <br />Fan Motors Qty: 2 <br />Fan Motor FLA: 0.8 Amps <br />Notice: Outdoor unit elect. data is based on 460-3-60 <br />Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage <br />Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage <br />Acoustics <br />Sound Power Levels, db re 10E-12 Watts <br />A -Weighted Outdoor Unit (dB) Indoor Unit <br />(dB,Ducted) <br />Total Level 83.4 NA <br />163Hz 38.6 NA <br />1125Hz 52.8 NA <br />10/10/2024 <br />09:24AM <br />Commercial Split Systems Builder 1.67 Page 5 of 15 <br />