UTILITY PLAN NOTES <br />1. ALL STORM SEWER, SANITARY SEWER AND WATERMAIN UTILITIES SHALL BE FURNISHED AND <br />INSTALLED PER THE REQUIREMENTS OF THE SPECIFICATIONS,THE MINNESOTA PLUMBING <br />CODE, THE LOCAL GOVERNING UNIT, AND THE STANDARD UTILITIES SPECIFICATION OF THE <br />CITY ENGINEERS ASSOCIATION OF MINNESOTA (CEAM), CURRENT EDITION. <br />2. ALL UTILITY PIPE BEDDING SHALL BE COMPACTED SAND OR FINE GRANULAR MATERIAL. ALL <br />COMPACTION SHALL BE PERFORMED PER THE REQUIREMENTS OF THE CEAM SPECIFICATION <br />AND THE GEOTECHNICAL REPORT. <br />3. ALL CONNECTIONS TO EXISTING UTILITIES SHALL BE PERFORMED PER THE REQUIREMENTS OF <br />THE STATE AND LOCAL JURISDICTIONS. THE CITY DEPARTMENT OF ENGINEERING AND <br />BUILDING INSPECTIONS DEPARTMENT AND THE CONSTRUCTION ENGINEER MUST BE NOTIFIED <br />AT LEAST 48 HOURS PRIOR TO ANY WORK WITHIN THE PUBLIC RIGHT OF WAY, OR WORK <br />IMPACTING PUBLIC UTILITIES. <br />4. ALL SITE UTILITY SERVICES SHALL TERMINATE 5' FROM THE EXTERIOR BUILDING WALL UNLESS <br />OTHERWISE NOTED. THE SITE UTILITY CONTRACTOR SHALL COORDINATE WITH THE GENERAL <br />CONTRACTOR, MECHANICAL CONTRACTOR AND MECHANICAL ENGINEER TO DETERMINE THE <br />RESPONSIBILITY OF BRINGING THE SERVICE(S) INTO THE BUILDING, INSPECTIONS AND TESTING <br />PER APPLICABLE GOVERNING AGENCIES. <br />5. ALL NEW WATERMAIN AND SERVICES MUST HAVE A MINIMUM OF 8.0 FEET OF COVER. EXTRA <br />DEPTH MAY BE REQUIRED TO MAINTAIN A MINIMUM 18" VERTICAL SEPARATION TO SANITARY <br />OR STORM SEWER LINES. THE CONTRACTOR SHALL FIELD ADJUST WATERMAIN TO AVOID <br />CONFLICTS WITH SANITARY SEWER, STORM SEWER, AND SERVICES AS REQUIRED. INSULATION <br />OF WATERMAIN AND SANITARY SEWER LINES SHALL BE PROVIDED WHERE 8.0 FEET MINIMUM <br />DEPTH CAN NOT BE ATTAINED. <br />6. PER MINNESOTA DEPARTMENT OF LABOR & INDUSTRY REQUIREMENTS, A MINIMUM OF 18 <br />INCHES OF VERTICAL SEPARATION AND 10 FEET OF HORIZONTAL SEPARATION IS REQUIRED <br />FROM WATERMAIN TO ANY MANHOLE, SEPTIC SYSTEM, CATCH BASIN, SEWER PIPE, OR OTHER <br />SOURCE OF CONTAMINATION, MEASURED FROM THE OUTER EDGE OF THE PIPE TO THE OUTER <br />EDGE OF THE CONTAMINATION SOURCE UNLESS OTHERWISE SHOWN. <br />7. ALL STORM SEWER DOWNSPOUT COLLECTION PIPES AND WYES SHALL BE PVC (SCHEDULE 40). <br />8. CONTRACTOR TO SUBMIT SHOP DRAWINGS OF SANITARY & STORM STRUCTURE(S) AND <br />UNDERGROUND SYSTEM(S), AS APPLICABLE, FOR ENGINEER'S REVIEW. <br />9. CONTRACTOR TO VERIFY UNDERLYING SOILS BENEATH ALL STORMWATER FACILITIES, AND <br />PROVIDE DOCUMENTATION TO THE ENGINEER, PRIOR TO CONSTRUCTION OF THE FACILITIES. <br />10. ALL PORTIONS OF THE SANITARY & STORM SEWER SYSTEMS, INCLUDING CATCH BASINS, <br />LOCATED WITHIN 10 FEET OF THE BUILDING OR WATER SERVICE LINE MUST BE TESTED <br />ACCORDANCE WITH MINNESOTA RULES, PART 4714. <br />11. ALL FIRE HYDRANTS SHALL BE LOCATED 5 FEET BEHIND BACK OF CURB OR EDGE OF PAVEMENT <br />UNLESS OTHERWISE NOTED. <br />z <br />D ' <br />•� <br />O <br />O Lifts <br />( <br />Q� <br />RIZ <br />D <br />13 <br />CB <br />RIM=869.53 <br />INV=864.75 <br />(8"DIP) <br />CB <br />RIM=871.26 <br />INV=867.93 <br />12. HYDRANT USE: CONTRACTOR IS NOT ALLOWED TO USE HYDRANT(S). THIS ALSO APPLIES TO <br />SUBCONTRACTORS. THE CITY HAS TWO WATER FILL STATIONS AVAILABLE. ELMCREST PARK FILL <br />STATION & PUBLIC WORKS WATER FILL STATION. PLEASE COORDINATE WITH PUBLIC WORKS. <br />13. OPERATING VALVES FOR TURNING WATER MAIN ON/OFF: PUBLIC UTILITIES DEPARTMENT WILL <br />OPERATE ALL VALVES AND FILL ALL WATER MAINS (PUBLIC AND PRIVATE). CONTRACTOR SHALL <br />GIVE AT LEAST 24 HOURS NOTICE TO HAVE WATER SHUT OFF AND SHALL NOTIFY IN WRITING, <br />ALL AFFECTED CUSTOMERS AT LEAST 24 HOURS IN ADVANCE BEFORE SHUT OFF; ATTACH TO <br />DOOR, ETC., NOT IN MAILBOXES. <br />14. TEMPORARY SERVICE: THE CONTRACTOR SHALL PROVIDE TEMPORARY SERVICE IF SERVICE <br />CANNOT BE RESTORED SAME DAY. IF USING HYDRANT FOR TEMPORARY SERVICE, NOTIFY <br />PUBLIC UTILITIES DEPARTMENT AND USE ONLY PRE -APPROVED HYDRANT AND SUPPLIED <br />HYDRO METER WITH BACK FLOW. THE CONTRACTOR'S TEMPORARY MAIN SHALL BE <br />DISINFECTED, FLUSHED AND BACTERIOLOGICAL ANALYSIS SHOWN NEGATIVE PRIOR TO <br />PUTTING THE TEMPORARY SYSTEM IN SERVICE. THE TEMPORARY WATER SYSTEM SHALL BE IN <br />PLACE PRIOR TO THE PUBLIC UTILITIES DEPARTMENT SHUTTING OFF ANY WATER MAINS. <br />15. REFER TO GEOTECHNICAL EVALUATION REPORT (REPORT B2505962), DATED SEPTEMBER 11, <br />2025 AS PREPARED BY BRAUN INTERTEC, FOR AN EXISTING SUBSURFACE SITE CONDITION <br />ANALYSIS AND CONSTRUCTION RECOMMENDATIONS INCLUDING BUT NOT LIMITED TO: <br />A. <br />B. <br />C. <br />D. <br />E. <br />F. <br />G. <br />REUSE OF ON -SITE SOILS <br />GROUNDWATER AND RECOMMENDATIONS FOR EXCAVATION DEWATERING. <br />SITE GRADING AND SUBGRADE PREPARATION. <br />PAVEMENTS AND EXTERIOR SLABS. <br />TRENCH EXCAVATION AND BACKFILL. <br />EXTERIOR UTILITY SUPPORTS. <br />FROST PROTECTION. <br />16. CONTRACTOR SHALL PROVIDE AS -BUILT INFORMATION OF CONSTRUCTED UTILITIES <br />(RECOMMENDED PRIOR TO BACKFILLING) PER APPLICABLE PERMIT REQUIREMENTS AND/OR <br />DEVELOPMENT AGREEMENTS. <br />17. ALL UNUSED UTILITY SERVICES SHALL BE ABANDONED PER THE REQUIREMENTS OF THE <br />APPLICABLE GOVERNING AGENCIES. <br />18. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL REQUIRED UTILITY PERMITS FROM THE <br />APPLICABLE GOVERNING AGENCIES. <br />19. DUCTILE IRON PIPE (DIP) WATERMAIN: 6" OR LESS IN DIAMETER SHALL BE CLASS 53, 8" OR <br />LARGER IN DIAMETER SHALL BE CLASS 52. <br />4 <br />8" GV <br />(SEE DETAIL) <br />4 <br />4 <br />4 <br />co <br />4 <br />4 <br />7 COMBINED 8" DOMESTIC & FIRE <br />PROTECTION WATER SERVICE STUB <br />(COORDINATE W/ MECHANICAL) <br />(VERIFY SIZE, INVERT, & LOCATION W/ <br />12" ROOF DRAIN STUB <br />(VERIFY SIZE, LOCATION, <br />AND INV W/ MECHANICAL) <br />PROPOSED <br />BUILDING <br />FFE=872.76 <br />(COORDINATE WITH <br />APPROXIMATE LOCATION OF FDC <br />(COORDINATE W/ MECHANICAL) <br />(8"DIP) <br />4 <br />4 <br />4 <br />44 <br />4 <br />El <br />4 <br />Ramsey Parkway NW <br />(Publicly Traveled Roadway) <br />CONNECT TO EXISTING 8" WATERMAIN STUB <br />(FIELD VERIFY SIZE, LOCATION, & MATERIAL) <br />Ad <br />8 LF 8" DIP WATERMAIN <br />PROPOSED <br />BUILDING <br />FFE=875.76 <br />GFE=864.76 <br />(COORDINATE WITH <br />48 LF 12" PVC <br />CBMH 11 <br />RIM=869.93 <br />INV(N)=865.49 <br />INV(SE)=865.49 <br />"6 <br />] 68 LF 6" DIP WATERMAIN <br />Lr <br />Ingress <br />89 LF 12" PVC <br />4 <br />4 <br />12" ROOF DRAIN STUB <br />/ <br />(VERIFY SIZE, LOCATION, <br />AND INV W/ MECHANICAL) <br />and Egress <br />INV=867.71-\ <br />42 LF 8" PVC <br />49 LF 18" HDPE <br />@ 0.50% <br />4 <br />4 <br />4 <br />4 <br />4 <br />INV=868.79 <br />33 LF 8" PVC <br />8"X8" STORM WYE <br />STMH 10 <br />RIM=870.85 <br />INV(NW)=865.25 <br />INV(E)=865.25 <br />FIRE HYDRANT & 6" GV-TYP. <br />(SEE DETAIL) <br />\_ 54 LF 8" PVC <br />4 <br />EXTEND EX. SANITARY <br />SEWER SERVICE <br />INV(S)= 859.56± <br />(FIELD VERIFY EX. <br />LOCATION, SIZE, & INV.) <br />4 <br />4 <br />4 <br />oo <br />-A‘& A <br />STUB MARKER <br />INV=(859.15) <br />33 LF 8" PVC <br />8"X8" STORM WYE <br />228 LF 18" HDPE <br />as shown on WATERFONT VILLAGE Doc. No. 618840.0 <br />RIM=867. <br />- CB 5 <br />CONNECT TO EXISTING 8" WATERMAIN W/ WET TAP <br />(FIELD VERIFY SIZE, LOCATION, & MATERIAL) <br />Easement per Doc. No. 6125'39.010 <br />CB <br />RIM=868.46 <br />INV=862.23 <br />CBMH 4 <br />RIM=868.75 <br />PID#: 28-32-25-23-0024 <br />ADDRESS: 7895 SUNWOOD DRIVE NW, RAMSEY, MN 55303 <br />OWNER NAME: RAMSEY PROPERTIES LLC <br />USE: COMMERCIAL SUBDISTRICT <br />ZONING: COR-2B <br />SMH <br />INV=859.21 <br />A <br />ICB- <br />A <br />RIM=867.38 <br />INV=862.82 <br />CB <br />RIM=866 <br />A <br />A <br />A <br />A <br />A <br />A <br />CB <br />RIM=867.18 <br />INV=862.68 <br />CB <br />RIM=8 <br />INV- <br />10" SANITARY SEWER SERVICE <br />- INV=859.61 <br />(VERIFY LOCATION & INV. W/ MECHANICAL) <br />147 <br />146 LF 18" HDPE <br />"PVC) <br />I I - <br />12" ROOF DRAIN STUB <br />(VERIFY SIZE, LOCATION, <br />AND INV W/ MECHANICAL) <br />CBMH 3 <br />RIM=870.79 <br />CB <br />NO <br />PARKING <br />v‘l CB <br />TRENCH DRAIN 30 <br />RIM=864.26 <br />OUTLET=862.66 <br />INSTALL TIDEFLEX CHECKMATE <br />ULTRAFLEX INLINE CHECK VALVE <br />(SEE DETAIL) <br />6" 45 DEG. BEND - <br />13 LF 6" DIP WATERMAIN <br />6" 45 DEG. BEND <br />49 LF 6" DIP WATERMAIN <br />FIRE HYDRANT & 6"GV-TYP. <br />(SEE DETAIL) <br />6" 45 DEG. BEND <br />14 LF 6" DIP WATERMAIN <br />RIM=868.24 <br />INV=862.24 N <br />INV=861.54 S;W <br />100 LF 6" <br />DRAINTILE <br />6" 45 DEG. BEND <br />11 LF 6" DIP WATERMAIN <br />STMH 2 <br />RIM=870.81 <br />41 LF 12" HDPE <br />CBMH 20 <br />RIM=870.33 <br />4 <br />00 <br />41 LF 12" HDPE <br />10 N;S <br />AN; <br />STMH <br />RIM=869.37 <br />INV=(863.90) NE <br />(SI <br />---- CONNECT TO EX. STRUCTURE <br />@ INV(W)=862.24 <br />/ CB <br />RIM=867.66 <br />INV=863.76 <br />WATERMAIN UNDER RETAINING WALL '''/Z7 <br />(OR APPROVED EQUAL) <br />45 LF WATERMAIN INSULATION <br />61 LF 6" DIP WATERMAIN <br />CONNECT TO EXISTING 8" WATERMAIN STUB / <br />8"X6" REDUCER <br />(FIELD VERIFY SIZE, LOCATION, & MATERIAL) <br />21 LF 12" HDPE <br />re <br />BUILD STMH 1 OVER EX. <br />RIM=869.24 <br />INV(NW)=865.20 <br />SUMP=859.03 <br />(FIELD VERIFY <br />LOCATION & INVERT) <br />SCALE <br />LINE <br />20 <br />IN FEET <br />40 <br />LEGEND <br />EXISTING <br />0 <br />0 <br />FM <br />ELE <br />FO <br />GAS <br />TEL <br />OH <br />CATCH BASIN <br />STORM MANHOLE <br />FLARED END SECTION <br />SANITARY MANHOLE <br />HYDRANT <br />GATE VALVE <br />POST INDICATOR VALVE <br />WATER MANHOLE / WELL <br />LIGHT POLE <br />POWER POLE <br />ELECTRIC METER <br />GAS METER <br />TELEPHONE PEDESTAL <br />SIGN <br />BENCHMARK <br />SOIL BORING <br />PARKING STALL COUNT <br />ACCESSIBLE PARKING STALL <br />STORM SEWER <br />DRAINTILE <br />SANITARY SEWER <br />FORCEMAIN <br />WATERMAIN <br />SANITARY SEWER SERVICE <br />WATER SERVICE <br />UNDERGROUND ELECTRIC <br />UNDERGROUND FIBER OPTIC <br />UNDERGROUND GAS <br />UNDERGROUND TELEPHONE <br />OVERHEAD UTILITY <br />FENCE <br />CHAIN LINK FENCE <br />CONCRETE CURB <br />RETAINING WALL <br />CONCRETE <br />NO PARKING <br />BUILDING <br />CONTOUR <br />SPOT ELEVATION <br />DIRECTION OF FLOW <br />TREE LINE <br />PARKING SETBACK LINE <br />PROPOSED <br />:110 <br />• <br />4 <br />7979 <br />SUNWOOD DR. <br />MIXED -USE <br />7979 SUNWOOD DRIVE <br />RAMSEY, MN <br />ROERS <br />COMPANIES <br />:. LOUCKS <br />ELE <br />FO <br />TEL <br />OH <br />0-0- <br />BTL <br />NOTE: <br />EXISTING CONDITIONS INFORMATION <br />SHOWN IS FROM AN ALTA/NSPS LAND <br />TITLE SURVEY PREPARED BY LOUCKS, <br />CALL BEFORE YOU DIG! <br />Gopher State One Call <br />TWIN CITY AREA: 651-454-0002 <br />TOLL FREE: 1-800-252-1166 <br />WARNING: <br />THE CONTRACTOR SHALL BE RESPONSIBLE FOR CALLING FOR LOCATIONS OF ALL <br />EXISTING UTILITIES. THEY SHALL COOPERATE WITH ALL UTILITY COMPANIES IN <br />MAINTAINING THEIR SERVICE AND / OR RELOCATION OF LINES. <br />THE CONTRACTOR SHALL CONTACT GOPHER STATE ONE CALL AT 651-454-0002 AT <br />LEAST 48 HOURS IN ADVANCE FOR THE LOCATIONS OF ALL UNDERGROUND WIRES, <br />CABLES, CONDUITS, PIPES, MANHOLES, VALVES OR OTHER BURIED STRUCTURES BEFORE <br />DIGGING. THE CONTRACTOR SHALL REPAIR OR REPLACE THE ABOVE WHEN DAMAGED <br />DURING CONSTRUCTION AT NO COST TO THE OWNER. <br />CIVIL ENGINEERING <br />LANDSCAPE ARCHITECTURE <br />LAND SURVEYING <br />12755 Highway 55, Suite R100 <br />Plymouth, MN 55441 <br />763.424.5505 <br />CADD QUALIFICATION <br />CADD files prepared by the Consultant for this project are <br />instruments of the Consultant professional services for use solely <br />with respect to this project. These CADD files shall not be used <br />on other projects, for additions to this project, or for completion <br />of this project by others without written approval by the <br />Consultant. With the Consultant's approval, others may be <br />permitted to obtain copies of the CADD drawing files for <br />information and reference only. All intentional or unintentional <br />revisions, additions, or deletions to these CADD files shall be <br />made at the full risk of that party making such revisions, additions <br />or deletions and that party shall hold harmless and indemnify the <br />Consultant from any & all responsibilities, claims, and liabilities. <br />SUBMITTAL/REVISIONS <br />08/07/2025 SCHEMATIC PAGE FLIP <br />08/18/2025 LAND USE APPLICATION <br />08/22/2025 SCHEMATIC DESIGN <br />09/11/2025 CITY RESUBMITTAL <br />PROFESSIONAL SIGNATURE <br />I hereby certify that this plan, specification or <br />prepared by me or under my direct supervis <br />laws of the State of Minnesota. <br />Date 91V% <br />License <br />56088 <br />QUALITY CONTROL <br />Loucks Project <br />Project Lead <br />Drawn By <br />Checked By <br />Review Date <br />No. <br />250244.00 <br />SRT <br />LAH <br />SRT <br />09/10/2025 <br />SHEET INDEX <br />C1-1 EX. COND. & SITE DEMO PLAN <br />C1-2 CONST. STAGING PLAN <br />C2-1 <br />C2-2 <br />C2-3 <br />C3-1 <br />C3-2 <br />C3-3 <br />C4-1 <br />C8-1 - C8-3 <br />SITE PLAN <br />ACCESSIBLE ROUTE PLAN <br />TURNING MOVEMENTS <br />GRADING PLAN <br />SWPPP <br />SWPPP NOTES <br />UTILITY PLAN <br />CIVIL DETAILS <br />LANDSCAPE PLAN <br />LANDSCAPE DETAILS <br />UTILITY PLAN <br />C4-1 <br />