Laserfiche WebLink
B 1 b Mechanical Joints <br />The last eight inches (8") of the outside spigot surface and the inside bell surface of each pipe <br />and appurtenance joint shall be painted with a thin film of approved gasket lubricant after being <br />thoroughly cleaned. The gland shall then be slipped on the spigot end with the lip extension <br />toward the socket or bell end. The rubber gasket shall be kept in a warm, flexible condition at all <br />times, and for purposes of placement shall be painted with a thin film of approved gasket <br />lubricant and be placed on the spigot end with the thick edge toward the gland <br />After the spigot end is inserted into the socket to full depth and centered, the gasket shall be <br />pressed into place within the bell evenly around the entire joint. After the gland is positioned <br />behind the gasket, all bolts shall be installed and the nuts tightened alternately to the specified <br />torque, such as to produce equal pressure on all parts of the gland. <br />Unless otherwise specified, the bolts shall be tightened by means of a suitable torque -limiting <br />wrench to within a foot-pound range of: 45 to 60 for 5/8 inch bolts; 75 to 90 for 3/4 inch bolts; 85 <br />to 100 for 1 inch bolts; and 105 to 120 for 1-1/4 inch bolts. After tightening, all exposed parts of <br />the bolts and nuts shall be completely coated with an approved asphaltic type rust preventive <br />material. <br />81 c Flanged Joints <br />Flanged joints shall be installed only in above grade or exposed locations and shall conform to <br />the requirements of AV VVA C115 Specifications, the Plans, Specifications and Special <br />Provisions. Flanged joints shall have full face gaskets. <br />B2 Polyvinyl Chloride Pipe Joints <br />82a Push -On Joints <br />The circular rubber gasket shall be bonded to the inner wall of the gasket recess of the bell <br />socket. Installation of pipe spigot into the bell socket shall conform to the requirements for <br />Ductile Iron Push -On Joints as set forth under the provisions of 2611.3B1 a. <br />B3 Polyethylene Pipe Joints <br />Polyethylene pipe joints shall conform to the requirements of AVVWA C-906, and shall be made <br />by the Thermal Butt -Fusion Method, Mechanical Flange Adaptor Method, Mechanical Joint <br />Adaptor Method and Mechanical Transition Fittings. Mechanical joints shall include stainless <br />steel pipe stiffeners. Compression fittings are not allowed for pipe diameters greater than two <br />inches (2") in diameter. <br />B4 Tracer Wire for Non-conductive Pipe <br />Tracer wire shall be installed along the length of all non-conductive mainline pipes, laterals, and <br />services with vertical riser to the surface, at gate valve boxes, hydrants, curb boxes, and/or <br />utility location boxes as required by the Special Provisions. Tracer wire shall be taped, clamped <br />or affixed to the pipe in another manner as approved by the Engineer. <br />Page 31 <br />