Laserfiche WebLink
All tanks, regardless of material or method of construction, <br />shall conform to the following design criteria. <br />1. The liquid depth of any septic tank or compartment thereof <br />shall be not less tnau Lhirty (30) inches. A liquid depth <br />greater than six and one -half (6 -1/2) feet shall not be <br />considered in determining tank capacity. <br />2. No tank or compartment thereof shall have an inside <br />horizontal dimension less than twenty -four (24) inches. <br />3. Inlet and outlet connections of the tank shall be submerged <br />by means of baffles. <br />4. The volume in the tank between the liquid surface and the top <br />of the inlet and outlet baffles shall be not less than twenty per <br />cent (20%) of the total required liquid capacity, except that in <br />horizontal cylindrical tanks, this space shall be not less than <br />fifteen per cent (15%) of the total required liquid capacity. <br />5. Inlet and outlet baffles shall be constructed of acid <br />resistant concrete, acid resistant fiberglass, or plastic. <br />6. Sanitary tees shall be bonded to the inlet or outlet pipe. <br />Baffles shall be integrally cast with the tank, affixed with a <br />permanent waterproof adhesive, or affixed with stainless steel <br />connectors, top and bottom. <br />7. The inlet baffle shall extend at least six (6) inches, but <br />not more than twenty per cent (20%) of the total liquid depth <br />below the liquid surface and at least one (1) inch above the <br />crown of the inlet sewer. <br />8. The outlet baffle and the baffles between compartments shall <br />extend below the liquid surface a distance equal to forty per <br />cent (40%) of the liquid depth, except that the penetration of <br />the indicated baffles or sanitary tees for horizontal cylindrical <br />tanks shall be thirty -five per cent (35%) of the total liquid <br />depth. They also shall extend above the liquid surface as <br />required in 4 above. In no case shall they extend less than six <br />(6) inches above the liquid surface. <br />9. There shall be at least one (1) inch between the underside of <br />the top of the tank and the highest point of the inlet and outlet <br />devices. <br />10. The inlet invert shall be not less than three (3) inches <br />above the outlet invert. <br />11. The inlet and outlet shall be located opposite each other <br />along the axis of maximum dimension. The horizontal distance <br />between the nearest points of the inlet and outlet devices shall <br />be at least four (4) feet. <br />